AB-CO Controls AFP-03
|
|
|
• Suitable for up to three hundred (300) cubic foot volumes for Class 1 and 2, Division 2, Groups A, B, C, D, F, G - Z purge
• Suitable for up to three hundred (300) cubic foot volumes for Class 1 and 2, Division 2, Groups A, B, C, D, F, G - Y purge
• Outlet to enclosure 1/2-inch tube fitting. Use 1/2-inch OD x 0.035-inch wall tubing
• Required input flow capability thirty (40) SCFM
• Fast purge output flow 16 SCFM. Fast purge time 1 minute/ 10 cubic feet of enclosure volume (1 minute/4 cubic feet for motors).
• Standard maintenance flow rate 0.5 to 40 SCFH
|
|
|
|